Routine Inspection
PO Reference
PO-SLA-2026-001
SLA Type
Service
Fire Equipment
Quarterly Visit
2 of 4
Parent SLA
SLA-ARC-2026
Arcadia East Wing
PO Value
R18,500
(covers 4 visits)
Assessment
28 Apr 2026
Themba N.
Quotation
29 Apr 2026
Sarah B.
PO Issued
30 Apr 2026
Delta PF
Work Execution
5 May 2026
Themba N.
Invoicing
5 May 2026
Finance
Certification
6 May 2026
Lerato K.
Quarterly routine fire safety inspection covering all fire protection equipment and emergency systems.
Fire extinguisher pressure within range
All units tested - pressure normal
Extinguisher access unobstructed
Sprinkler heads undamaged
Visual inspection complete
Control panel showing no faults
Zone 3 showing intermittent fault E-04
Fire doors close fully and latch
All doors operational
Emergency lighting operational
Battery backup tested
Evacuation signage visible
Suppression system armed
System active and monitoring
Overall fire safety compliance is satisfactory. One issue identified: Zone 3 on the main control panel is displaying an intermittent E-04 fault code. This indicates a potential zone isolation or communication issue. Recommend scheduling a follow-up visit for panel diagnostics within 14 days. All fire extinguishers are within service date and pressure ranges. Emergency lighting passed 90-minute battery test.